GRAND SENSIBLE HEAT FACTOR

It is defined as the ratio of total sensible heat to the grand total heat which the cooling coil or conditioning apparatus is required to handle (Fig. 20.31).

images

where TSH = total sensible heat = RSH + OASH

TLH = total latent heat = RLH + OALH

GTH = grand total heat = TSH + TLH = (RSH OASH) + (RLH + OALH)

Let 1 = volume rare of outside air m3/min

td1td2 = DBT of outside and room air respectively, °C

w1w2 = specific humidity of outside and room air respectively kg/kg.d.a

h1h2 = enthalpy of outside and room air respectively, kJ/kg d.a

images
images

Outside air total heat, OATH = OASH + OALH

images

img

Figure 20.31 RSHF line estimation